Note:
When the ON/OFF function is selected for DC braking (DB), using the input terminal selection parameter,
you can judge the inverter to be normal if "" disappears when opening the circuit between the terminal and
CC.
[Prealarm display]
Overcurrent alarm
Overvoltage alarm
Overload alarm
Overheat alarm
If two or more problems arise simultaneously, one of the following alarms appears and blinks.
, , 
The blinking alarms , , ,  are displayed in this order from left to right.

13.2 Restoring the inverter from a trip

Do not reset the inverter when tripped because of a failure or error before eliminating the cause. Resetting the
tripped inverter before eliminating the problem causes it to trip again.
The inverter can be restored from a trip by any of the following operations:
(1) By turning off the power (Keep the inverter off until the LED turns off.)
Note: ⇒ See section 6.17.3 (inverter trip retention selection ) for details.
(2) By means of an external signal (Short circuit between RES and CC on terminal board → Open)
(3) By operation panel operation
(4) By inputting a trip clear signal from a remote input device
(Refer to the remote input device operating manual for details.)
To reset the inverter by operation panel operation, follow these steps.
1.
Press the
2.
Pressing the
In case of a trip due to overheating (), the inverter checks the temperature within. Wait until the
temperature in the inverter falls sufficiently before resetting the inverter.
[Caution]
Turning the inverter off then turning it on again resets the inverter immediately. You can use this mode of
resetting if there is a need to reset the inverter immediately. Note, however, that this operation may damage
the system or the motor if it is repeated frequently.
Same as  (overcurrent)
Same as  (overvoltage)
Same as  and  (overload)
Same as  (overheat)
key and make sure that  is displayed.
STOP
key again will reset the inverter if the cause of the trip has already been eliminated.
STOP
M-5
E6581381
13