Note 4: For IEC, the wire sizes specified in the above table apply to PVC wires (cupper wires shielded with an
Note 5: If there is a need to bring the inverter into UL compliance, use wires specified in Chapter 9.
Selection of wiring devices
Voltage class
Three-phase
200V class
Three-phase
400V class
Note 4)
10
Note 1: Selections for use of the Toshiba 4-pole standard motor with power supply voltage of 200V/400V-50Hz.
Note 2: Choose the MCCB according to the power supply capacity.
Note 3: When using on the motor side during commercial-power supply operation, choose the MC with class
Note 4: Attach surge killers to the magnetic contactor and exciting coil of the relay.
Note 5: In the case the magnetic contactor (MC) with 2a-type auxiliary contacts is used for the control circuit,
insulator with a maximum allowable temperature of 70°C) used at an ambient temperature of 40°C or less
For Japan, the wire sizes specified in the above table apply to HIV wires (cupper wires shielded with an
insulator with a maximum allowable temperature of 75°C) used at an ambient temperature of 40°C or less.
Input current (A)
Capacity of
applicable
motor
(kW)
200V class:200V
400V class:380V
0.4
1.9
0.75
3.3
1.5
6.1
2.2
8.7
4
15.7
5.5
20.8
7.5
27.9
11
42.1
15
56.1
18.5
67.3
22
80.4
30
113.3
0.4
1.0
0.75
1.7
1.5
3.2
2.2
4.6
4
8.1
5.5
10.9
7.5
14.7
11
21.1
15
28.5
18.5
34.8
22
41.6
30
56.7
37
84
45
104
55
120
75
167
For comply with UL and CSA standard, use the fuse certified by UL and CSA.
AC-3 rated current for the motor rated current.
raise the reliability of the contact by using 2a-type contacts in parallel connection.
Inverter model
200V class:240V
400V class:480V
1.6
VFFS1-2004PM
VFFS1-2007PM
2.7
VFFS1-2015PM
5.1
VFFS1-2022PM
7.3
VFFS1-2037PM
13.0
VFFS1-2055PM
17.3
VFFS1-2075PM
23.3
VFFS1-2110PM
34.4
VFFS1-2150PM
45.5
55.8
VFFS1-2185PM
66.4
VFFS1-2220PM
89.5
VFFS1-2300PM
VFFS1-4004PL
0.8
VFFS1-4007PL
1.4
VFFS1-4015PL
2.5
VFFS1-4022PL
3.6
VFFS1-4037PL
6.4
VFFS1-4055PL
8.6
VFFS1-4075PL
11.7
VFFS1-4110PL
16.8
VFFS1-4150PL
22.8
VFFS1-4185PL
27.8
VFFS1-4220PL
33.1
VFFS1-4300PL
44.7
VFFS1-4370PL
69
85
VFFS1-4450PL
101
VFFS1-4550PL
137
VFFS1-4750PL
J-2
E6581381
Molded case circuit
breaker (MCCB)
Magnetic contactor
Earth leakage circuit
(MC)
breaker (ELCB)
Operational current(A)
Rated current (A)
AC-1
3
25
5
25
10
25
15
25
30
25
40
32
50
40
75
50
100
80
100
80
125
100
175
125
25
3
25
3
25
5
25
10
25
15
25
20
32
30
32
40
40
50
50
60
80
75
80
100
100
100
125
125
150
125
200
250

Advertisement