Advertisement

5.4

Meter setting and adjustment

 : Meter selection
 : Meter adjustment
• Function
The signal output from the FM terminal is an analog voltage signal.
For the meter, use either a full-scale 0-1mAdc ammeter or full-scale 0-7.5Vdc (or 10Vdc)-1mA voltmeter.
Switching to 0-20mAdc (4-20mAdc) output current can be made by turning the FM (SW2) slide switch to
the I position. When switching to 4-20mAdc current input, make adjustments using  (analog
output gradient) and  (analog output bias).
[Parameter setting]
Title
5


Function
Adjustment range
0: Output frequency
1: Output current
2: Set frequency
3: DC voltage
4: Output voltage command value
5: Input power
6: Output power
7: Torque
8: Torque current
9: Motor cumulative load factor
Meter
10: Inverter cumulative load factor
selection
11: - (Do not select)
12: Frequency setting value (after PID)
13: VIA Input value
14: VIB Input value
15: Fixed output 1 (Output current: 100%)
16: Fixed output 2 (Output current: 50%)
17: Fixed output 3
(Supposition output at =17)
18: RS485 communication data
19: For adjustments (set value is
displayed.)
Meter
-
adjustment
Supposition output at
=
Maximum frequency ()
1.5 times of rated current
Maximum frequency ()
1.5 times of rated voltage
1.5 times of rated voltage
1.85 times of rated power
1.85 times of rated power
2.5 times of rated torque
2.5 times of rated torque
Rated load factor
Rated load factor
Maximum frequency ()
Maximum input value
Maximum input value
E-10
E6581381
Default setting
0
-
-
-
-
FA51=1000
-
-
-