6.5.3
: External contact input - UP response time
: External contact input - UP frequency steps
: External contact input - DOWN response time
: External contact input - DOWN frequency steps
: Initial up/down frequency
: Change of the initial up/down frequency
• Function
6
Initial up/down frequency
* These functions take effect when parameter (frequency setting mode selection 1) is set to or
parameter (frequency setting mode selection 2) is set to is enabled.
Setting of frequency with the input from an external
contact
These parameters are used to set an output frequency by means of a signal from an external device.
Title
Function
External contact input - UP response
time
External contact input - UP frequency
steps
External contact input - DOWN
response time
External contact input - DOWN
frequency steps
Change of the initial up/down
frequency
Adjustment with continuous signals (Parameter-setting example 1)
Set parameters as follows to adjust the output frequency up or down in proportion to the frequency
adjustment signal input time:
Panel frequency incremental gradient = / setting time
Panel frequency decremental gradient = / setting time
Set parameters as follows to adjust the output frequency up or down almost in synchronization with the
adjustment by the panel frequency command:
= = 1
( / (or )) ≥ ( / setting time)
( / (or )) ≥ ( / setting time)
Adjustment range
0.0 - 10.0 (s)
0.0 - FH (Hz)
0.0 - 10.0 (s)
0.0 - FH (Hz)
LL - UL (Hz)
0: Not changed
1: Setting of changed
when power is turned off
F-20
E6581381
Default setting
0.1
0.1
0.1
0.1
0.0
1