Toshiba TOSVERT VF-FS1 Instruction Manual page 65

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

[Parameter setting]
Title
Function
Acceleration time 1

Deceleration time 1

Note: When the acceleration/deceleration time is set at 0.0 seconds, the inverter speed increases or reduces
speed within 0.05 seconds.
If the programmed value is shorter than the optimum acceleration/deceleration time determined by load
conditions, overcurrent stall or overvoltage stall function may make the acceleration/deceleration time
longer than the programmed time. If an even shorter acceleration/deceleration time is programmed, there
may be an overcurrent trip or overvoltage trip for inverter protection.
⇒ For further details, see section 13.1.
Adjustment range
0.0-3200 sec.
0.0-3200 sec.
E-3
E6581381
Default setting
According to model
(⇒ See page K-14)
According to model
(⇒ See page K-14)
5