6.14 Conducting PID control

 : PID control waiting time
 : PID control
 : Proportional gain
 : Integral gain
 : Differential gain
 : PID forward / reverse characteristic selection
• Function
[Parameter setting]
6






1) External connection
Using feedback signals (4 to 20mA, 0 to 10V) from a detector, process control can be exercised, for
example, to keep the airflow, amount of flow or pressure constant.
Title
Function
PID control waiting time
PID control
Proportional gain
Integral gain
Differential gain
PID forward / reverse characteristic
selection
Adjustment range
0-2400 [s]
0: Disabled
1: Enabled (Feedback: VIA)
2: Enabled (Feedback: VIB)
0.01-100.0
0.01-100.0
0.00-2.55
0:Forward (Standard)
1:Reverse
F-44
E6581381
Default setting
0
0
0.30
0.20
0.00
0