Toshiba TOSVERT VF-FS1 Instruction Manual page 70

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

 : Command mode selection
 : Frequency setting mode selection 1
• Function
Remote mode selection, these parameters are used to specify which input device (operation panel,
terminal board, RS485 communication) takes priority in entering an operation stop command or a
frequency setting command, VIA, VIB, operation panel, RS485 communication device, external contact
up/down).
At Local mode selection, the start/stop operation and frequency setting by operation panel is prior with no
relation of /setting.
<Command mode selection>
Title

5
Programmed value
:
:

* There are two types of function: the function that conforms to commands selected by , and the function
that conforms only to commands from the terminal board.
⇒ See the table of input terminal function selection in Chapter 11.
* When priority is given to commands from a linked computer or terminal board, they have priority over the
setting of .
Function
Command mode selection
Terminal board
ON and OFF of an external signal Runs and stops operation.
operation
Operation panel
Press the
operation
Serial communication
Run and stop through serial communication.
operation
Adjustment range
0: Terminal board
1: Operation panel
2: RS485 communication
and
keys on the operation panel to start and stop.
RUN
STOP
E-8
E6581381
Default setting
0