[0: Supply voltage uncorrected, output voltage limited]
0
Output frequency
* The above applies when V/F control mode selection
parameter is set to "0" or "1".
* The output voltage can be prevented from exceeding
the input voltage.
[2: Supply voltage uncorrected, output voltage unlimited]
0
Output frequency
* The above applies when V/F control mode selection
parameter is set to "0" or "1".
* The output voltage can be prevented from exceeding
the input voltage.
6.12.6 Canceling the operation command
: Reverse-run prohibition
• Function
This function prevents the motor from running in the forward or reverse direction when it receives the
wrong operation signal.
[Parameter setting]
Title
Reverse-run prohibition
[1: Supply voltage corrected, output voltage limited]
Input voltage
High
Low
[3: Supply voltage corrected, output voltage unlimited]
Input voltage
High
Low
* Even if is set for an output voltage lower than the input
voltage, the output voltage will exceed the voltage adjusted
by when the output frequency is higher than the base
frequency 1 .
Function
0: Forward/reverse run permitted
1: Reverse run prohibited
2: Forward run prohibited
F-41
0
Output frequency
0
Output frequency
Adjustment range
E6581381
Input voltage
High
Low
Input voltage
High
6
Low
Default setting
0