Toshiba TOSVERT VF-FS1 Instruction Manual page 171

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

Example of setting 2
When =1.00 (Hz), and =1:
Each time you press the
(Hz) and also the value displayed on the operation panel changes in steps of 1. Use these settings to hide
decimal fractions and also the value displayed on the operation panel changes in steps of 1. Use these
settings to hide decimal fractions.
6.20.5 Changing the item displayed by default
 : Standard monitor display selection
• Function
This parameter specifies display format while power is on.
Changing the display format while power is on
When the power is on, the standard monitor mode displays the operation frequency (default setting) in the
format of "" or "". This format can be changed to any other monitor display format by setting
. This new format, however, will not display an assigned prefix such as  or .
[Parameter setting]
Title
Standard monitor display

selection
For more information on the  option "," refer to "Communications Function Instruction
Manual."
key, the frequency setting  changes in steps of 1Hz: 0 → 1 → 2 → ... → 60
Function
0: Operation frequency (Hz/free unit/step)
1: Frequency command (Hz/free unit/step)
2: Output current (%/A)
3: Inverter rated current (A)
4: Inverter load factor (%)
5: Output power (kW)
6: Frequency command after PID control
(Hz/free unit/step)
7: Optional item specified from an external
control unit
8: Output speed
9: Communication counter
10: Normal state communication counter
F-79
Adjustment range
E6581381
6
Default setting
0