● When the auxiliary power supply is obtained through the PCS terminal, if the
● Obtain the AC auxiliary power from the mains or a reliable power supply. Do
Step 1 Remove the RCM panel.
Step 2 Remove the mains AC input terminal cover.
Step 3 Connect the auxiliary power supply cables:
Figure 7-2 Connecting auxiliary power supply cables (directly from the mains)
Issue 01 (2024-07-31)
NO TICE
general power distribution switch on the customer side is turned off, the ESS
auxiliary power supply will be disconnected.
not directly obtain power from the AC side of renewable energy inverters such
as PV inverters and wind power converters.
When the auxiliary power supply is obtained directly from the mains, route
the AC power cables through the cable hole at the bottom and connect the
cables to the mains AC input terminal. The ESS is connected to an external
power distribution cabinet.
When the auxiliary power supply is obtained through the PCS terminal,
connect the M6 OT terminal to the mains AC input terminal and the M4 OT
terminal to the PCS.
Copyright © Huawei Digital Power Technologies Co., Ltd.
7 Installing Cables