Step 3 Turn on the RCCB on the RCM.
Step 4 Check that the AC voltages of the mains input terminals (MAINS), UPS input
terminals (UPS), and PCS input terminals in sequence are within the normal
ranges using a multimeter.
Step 5 Turn on the mains AC input switch QF1 on the RCM.
Step 6 (Optional) Turn on the UPS AC input switch QF2 on the RCM. This operation is
required when a UPS is configured.
Step 7 (Optional) Turn on the RCM disconnector (hold the handle with your left hand
and keep your left hand palm facing upward). This operation is required when a
disconnector is configured.
Step 8 (Optional) Turn on the ESS power switch on the UPS side. This operation is
required when a UPS is configured.
----End
Issue 01 (2024-07-31)
Copyright © Huawei Digital Power Technologies Co., Ltd.
8 Powering On the ESS