Address
Name
Words
Bits
A402
A402.00
Other Non-fatal
Error Flag (Sys-
tem Work Mem-
ory Error)
A402.02
Special I/O Unit
Setting Error
Flag
(Non-fatal error)
A402.03
CPU Bus Unit
Setting Error
Flag
(Non-fatal error)
CJ2 CPU Unit Software User's Manual
Function
• ON when a non-fatal error other than a non-fatal error allocated
to A402.01 to A402.15 occurs. (E.g., When an error occurs in
memory for online editing.)
• Details of the other non-fatal errors are stored in A315.
ON when an installed Special I/O Unit does not match the Special
I/O Unit registered in the I/O table. The CPU Unit will continue
operating and the ERR/ALM indicator on the front of the CPU Unit
will flash.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
The unit number of the Unit where the setting error occurred is
indicated in A428 to A433.
ON when any of the following occur for a Unit registered in the
synchronous unit operation settings.
• The Unit does not support the synchronous unit operation func-
tion.
• The Unit is not connected in the PLC.
• The Unit is not in the CPU Rack (i.e., it is in an Expansion
Rack).
The CPU Unit will continue operating and the ERR/ALM indicator
on the front of the CPU Unit will flash.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared and the cor-
rect PLC Setup is transferred to the CPU Unit.
The unit number of the Unit where the setting error occurred is
indicated in A428 to A433.
ON when an installed CPU Bus Unit does not match the CPU Bus
Unit registered in the I/O table. The CPU Unit will continue operat-
ing and the ERR/ALM indicator on the front of the CPU Unit will
flash.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
The unit number of the Unit where the setting error occurred is
written to A427
Appendices
Status
Write timing/
Status at
after mode
Related flags, set-
startup
change
tings
Cleared for
Cleared
---
error clear
operation.
Cleared
Cleared
A428 to A433
Cleared
Cleared
A427
A-137