Omron CJ2 CPU UNIT SOFTWARE User Manual page 622

Cj2 cpu unit software
Hide thumbs Also See for CJ2 CPU UNIT SOFTWARE:
Table of Contents

Advertisement

Appendices
Address
Name
Words
Bits
A402
A402.04
Battery Error
Flag
(Non-fatal error)
A402.06
Special I/O Unit
Error Flag
(Non-fatal error)
A402.07
CPU Bus Unit
Error Flag
(Non-fatal error)
A402.10
PLC Setup Error
Flag
(Non-fatal error)
A402.12
Basic I/O Unit
Error Flag
(Non-fatal error)
A402.13
Duplicate
Refresh Error
Flag
(Non-fatal error)
A-138
Function
ON if the CPU Unit's battery is disconnected or its voltage is low
and the Detect Battery Error setting has been set in the PLC
Setup.
The CPU Unit will continue operating and the ERR/ALM indicator
on the front of the CPU Unit will flash.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
This flag can be used to control an external warning light or other
indicator to indicate that the battery needs to be replaced.
ON when an error occurs in a data exchange between the CPU
Unit and a Special I/O Unit (including an error in the Special I/O
Unit itself).
The CPU Unit will continue operating and the ERR/ALM indicator
on the front of the CPU Unit will flash. The Special I/O Unit where
the error occurred will stop operating.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
The unit number of the Unit where the data exchange error
occurred is indicated in A418 through A423.
ON when an error occurs in a data exchange between the CPU
Unit and an CPU Bus Unit (including an error in the CPU Bus Unit
itself).
The CPU Unit will continue operating and the ERR/ALM indicator
on the front of the CPU Unit will flash. The CPU Bus Unit where
the error occurred will stop operating.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
The unit number of the Unit where the data exchange error
occurred is indicated in A417.
ON when there is a setting error in the PLC Setup. The CPU Unit
will continue operating and the ERR/ALM indicator on the front of
the CPU Unit will flash. The location of the error will be written to
A406.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
It will also turn OFF for a setting error for synchronous unit opera-
tion settings if correct settings are transferred to the Synchronous
Unit.
ON when an error has occurred in a Basic I/O Unit.
The CPU Unit will continue operating and the ERR/ALM indicator
on the front of the CPU Unit will flash.
ON: Error
OFF: No error
This flag will be turned OFF when the error is cleared.
The location of the error will be written to A408.
ON when the Detect Duplicate Refresh Errors parameter in the
PLC Setup is set to detect duplicate refresh errors and one of the
following occurs for the same Special I/O Unit.
• FIORF(225), IORF(097), IORD(222) or IOWR(223) in a cyclic
task is competing with FIORF(225), IORF(097), IORD(222) or
IOWR(223) in an interrupt task.
• FIORF(225), IORF(097), IORD(222) or IOWR(223) was exe-
cuted in an interrupt task when I/O was being refreshed.
If cyclic refreshing is not disabled in the PLC Setup for a Special
I/O Unit and FIORF(225), IORF(097), IORD(222) or IOWR(223) is
executed for the same Special I/O Unit in an interrupt task, a
duplicate refresh error will occur.
Status
Write timing/
Status at
after mode
Related flags, set-
startup
change
tings
Cleared
Cleared
PLC Setup (Detect
Battery Error)
Cleared
Cleared
A418 to A423
Cleared
Cleared
A417
Cleared
Cleared
A406
Cleared
Cleared
A408
Cleared
Cleared
A426,
PLC Setup
(Detect Duplicate
Refresh Errors
parameter in the
PLC Setup is set to
"Detect")
CJ2 CPU Unit Software User's Manual