Appendices
Address
Name
Words
Bits
A438
---
Pulse Output 2
Stop Error Code
A439
---
Pulse Output 3
Stop Error Code
A440
---
Max. Interrupt
Task Processing
Time
A441
---
Interrupt Task
With Max. Pro-
cessing Time
A-142
Function
If a Pulse Output Stop Error occurs for pulse output 2, the error
code is written to this word.
If a Pulse Output Stop Error occurs for pulse output 3, the error
code is written to this word.
Contains the Maximum Interrupt Task Processing Time in units of
0.1 ms.
(This value is written after the interrupt task with the max. pro-
cessing time is executed and cleared when PLC operation
begins.)
Disabled when high-speed interrupt function is enabled in the
PLC Setup.
Contains the task number of the interrupt task with the maximum
processing time. Hexadecimal values 8000 to 80FF correspond to
task numbers 00 to FF. Bit 15 is turned ON when an interrupt has
occurred.
(This value is written after the interrupt task with the max. pro-
cessing time is executed and cleared when PLC operation
begins.)
Disabled when high-speed interrupt function is enabled in the
PLC Setup.
Status
Write timing/
Status at
after mode
Related flags, set-
startup
change
tings
Retained
Cleared
• Cleared when an
origin search is
started.
• Refreshed when
a fatal pulse out-
put error occurs
during an origin
search.
• Refreshed when
the limit input sig-
nal for pulse out-
put is set to be
always enabled in
the PLC Setup
and pulse output
is stopped due to
the limit input.
• Cleared when
both limit inputs
are disabled and
a fatal pulse out-
put error code is
stored.
Retained
Cleared
• Cleared when an
origin search is
started.
• Refreshed when
a fatal pulse out-
put error occurs
during an origin
search.
• Refreshed when
the limit input sig-
nal for pulse out-
put is set to be
always enabled in
the PLC Setup
and pulse output
is stopped due to
the limit input.
• Cleared when
both limit inputs
are disabled and
a fatal pulse out-
put error code is
stored.
Cleared
Cleared
See Function col-
umn.
Cleared
Cleared
See Function col-
umn.
CJ2 CPU Unit Software User's Manual