Setup

Wire PLC Outputs

Configure up to two PLC outputs to indicate the
following states:
InvisiPac System Ready
Error Present
Maintenance Due
PLC #1
PLC #2
F
. 15: Dry Contact Outputs (24VDC/240VAC, 2A MAX) (J11)
IG
24
DRY CONTACT OUTPUTS
(24VDC / 240VAC, 2A MAX)
J11
1
2
3
4
PLC Output Specifications
Item
Specification
Output Type
Dry Contact (Open/Close Circuit)
Max Voltage
24 VDC / 240 VAC
Max Current
2A
1. Access the Electrical Enclosure. Follow the steps
on page 83.
2. Route a multi-conductor cable through one of the
I/O cable glands (207).
3. Wire PLC outputs to the system J11 on the AMZ.
4. Set PLC Settings on the ADM. Follow the steps
on page 25.
ti31252a
3A7259C