Dry Contact Inputs Wiring (Open/Closed
Circuit)
Item
Specifications
Dry Contact
Open/Closed Circuit
Signal Low: Open Circuit
Signal High: Closed Circuit
6
1
(5, 4, 3, 2)
F
. 14: Dry Contact Inputs (Open/Closed Circuit) Wiring (J8 and J9)
IG
3A7259C
1. Access the Electrical Enclosure. Follow the steps
on page 83.
2. Connect a jumper wire (16-28 AWG) between "-"
terminal on J8 and "ISO GND" terminal on J9.
3. Connect one side of the input to one of the "+"
terminals on J8. Connect the other side of the input
to the desired input terminal on J9 (labeled by input
number). Repeat for remaining inputs.
J8
24V
+
+
-
J9
ISO
GND
1
2
3
4
5
6
Setup
ti31249a
23