Power Cord Specifications; Breaker Characteristics - Fujitsu ORACLE M10-1 Installation Manual

Hide thumbs Also See for ORACLE M10-1:
Table of Contents

Advertisement

2.9.2

Power cord specifications

Table 2-10
and PCI expansion unit.
Table 2-10     Power cords and connector shape
Destination
Japan
North America
South America
China
Hong Kong
Taiwan
Korea
India
Other countries
2.9.3

Breaker characteristics

The breaker characteristics for the SPARC M10 systems must be taken into
consideration to allow the devices to be used under the right conditions. Use circuit
breakers that meet the following special conditions for the distribution panel
breakers on the equipment side.
 
Table 2-11
Table 2-11     Distribution panel breaker capacity on the equipment side
Device name
SPARC M10-1
PCI expansion unit
Fujitsu M10-1/SPARC M10-1 Installation Guide ・ March 2019
30
shows the power cords and the connector shapes for the SPARC M10-1
Power cord type
NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
NEMA 5-15P 125V 15A
NEMA L6-15P 250V 15A
IEC60320-C14 250V 10A
IRAM2073 250V 10A
NBR14136 250V 10A
GB2099.1 250V 10A
BSI363A 250V 10A
CNS10917 250V 10A
KSC8305 250V 10A
IS1293 250V 16A
IEC 60309 IP44 250V 10A
IEC60320-C14 250V 10A
shows the distribution panel breaker capacity on the equipment side.
Power supply input
Single-phase 100 to 120 VAC
Single-phase 200 to 240 VAC
Single-phase 100 to 120 VAC
Single-phase 200 to 240 VAC
Connector shape
IEC 60320-C13
Distribution panel breaker capacity on
equipment side
For Japan/North
For Europe
America/other countries
12 A
-
10 A
10 A
10 A
-
10 A
10 A