Contaminant Conditions; Checking Acoustic Noise Levels - Fujitsu ORACLE M10-1 Installation Manual

Hide thumbs Also See for ORACLE M10-1:
Table of Contents

Advertisement

is stricter than the guidelines applied to indoor locations with more relaxed
environmental conditions such as general office environments. However, if the server
is installed in a server room, this condition is not difficult to meet because server
rooms utilize highly efficient moisture-proof materials and have fewer ventilation
cycles.
2.5.3

Contaminant conditions

Table 2-5
the SPARC M10 systems.
Table 2-5     Acceptable reference values for contaminants
Contaminant
Hydrogen sulfide (H2S)
Sulfurous acid gas (sulfur oxide) (SO2)
Hydrogen chloride (HCI)
Chlorine (CI2)
Hydrogen fluoride (HF)
Nitrogen dioxide (nitrogen oxide) (NO2)
Ammonia (NH3)
Ozone (O3)
Oil vapor
Dust
Seawater (salt damage)
2.6

Checking Acoustic Noise Levels

Table 2-6
The acoustic noise levels provided in
conditions.
Measurement environment: ISO 7779 compliant
Ambient temperature: 23°C
provides the acceptable reference values for contaminants with regard to
provides acoustic noise levels of the SPARC M10-1.
Chapter 2 Planning and Preparing for System Installation
Acceptable reference value
7.1 ppb or less
37 ppb or less
6.6 ppb or less
3.4 ppb or less
3.6 ppb or less
52 ppb or less
420 ppb or less
5 ppb or less
3
0.2 mg/m
or less
3
0.15 mg/m
or less
Do not install out at sea or within 500 m
(1,640.4 ft.) of the seashore.
(However, this does not apply if air
conditioning facilities do not use outside air.)