5-8

Reset

5-8-1

Reset Function

• Use the reset function to reset the trip status (output shutoff status caused by occurrence of error) of
the inverter.
• The reset function is executed by the
nal, Operation command (S06 bit 15:RST) via Modbus communication or the Alarm Reset Com-
mand (S14).
• When a reset is performed with the RUN command ON, the inverter may abruptly start depending
on the setting of the STOP Key Priority/Start Check Function (H96). When performing a reset opera-
tion, ensure that the RUN command is OFF. For details, refer to Start Check Function (When (H96)
= "2," "4") on page 7-81.
Parameter
No.
E01 to E05,
E98, E99
S14
S06
Related function
Reset by Operator
Reset alarms and cancel errors by pressing the
Reset from Terminal
When the state of the RS (reset) terminal is changed from OFF to ON, the alarm is reset and AL
(alarm output) output allocated to the multifunction output terminal is set to OFF. When it is next
changed from ON to OFF, the alarm display is erased and the error state is cleared. Ensure at least 10
ms as the time for turning the RS (reset) terminal ON. During normal operation, keep the terminal set
to OFF.
M1 Series Standard Type User's Manual (I669)
Function name
Input Terminal [DI1] Function
Selection to Input Terminal [DI7]
Function Selection
Alarm Reset Command
Operation command
key on the Operator, input terminal "8: RS (Reset)" termi-
Data
8: RS (Reset)
0: Disable
1: Alarm reset
bit 15: RST
Output Terminal [DO1] Function Selection (E20), Output Ter-
minal [DO2] Function Selection (E21), Output Terminal
[ROA, ROB] Function Selection (E27) = "99: AL (Alarm sig-
nal)"
key on the Operator.
5 Basic Settings
Default data
Unit
-
-
0
-
0
-
5-49
5