Omron M1 Series User Manual page 633

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

If other than "0: 4 to 20 mA Unipolar" is set to Input Terminal [AI2] Operation Selection (AII) (C40), this
function does not operate.
Parameter No.
H91
7-9-14
Automatic Energy-saving Operation Function
This function automatically adjusts the inverter output power during constant speed operation to the
minimum level. It is suitable for load with reduced torque characteristics, such as fans and pumps.
To perform energy-saving operation using this function, set Energy-saving Operation Function Selec-
tion (E124) to "1: Energy-saving operation."
When the automatic energy-saving operation is enabled, it is possible to select Enable during running
at constant speed, and Enable during running at constant speed and acceleration/deceleration with
Auto Energy Saving Operation Condition Selection (H67).
 
Because this function controls the output power to the minimum necessary level, the motor may stall if
the rapid load fluctuation, such as impact load, occurs, which may result in an overcurrent trip.
Parameter No.
E124
H67
7-9-15
Commercial Switching (CS)
Commercial operation and inverter operation are switched by the "CS" terminal (15: Commercial
switch).
When switching between commercial operation/inverter operation is performed in an external se-
quence, input the CS allocated to multifunction input in accordance with the operation chart below.
Then, the inverter can be started from the commercial power supply frequency regardless of the set
frequency of the inverter, and the motor during the commercial operation can be smoothly switched to
inverter operation.
This function is enabled when Drive Control Selection (F42/A14) = "0, 1, 3, 4."
When the power supply frequency is 50 Hz, use "15: CS" and when the power supply frequency is 60
Hz, use "16: SW60."
Parameter No.
F42/A14
M1 Series Standard Type User's Manual (I669)
Function name
Current Input Wire Break
Detection
Function name
Energy-saving Operation
Function Selection
Auto Energy Saving Oper-
ation Condition Selection
Function name
1st Drive Control
Selection/2nd Drive Control
Selection
Data
0.0: Disable alarm detection
0.1 to 60.0: Issue alarm after set time
Data
0: Disable energy-saving operation
1: Energy-saving operation
0: Enable only at constant speed
1: Enable in all modes
Data
0: IM V/f control
1: IM Dynamic torque vector con-
trol
3: IM V/f control with speed sen-
sor
4: IM Dynamic torque vector con-
trol with speed sensor
7 Other Functions
Default da-
Unit
ta
0.0
s
Default da-
Unit
ta
0
-
0
-
Default data
Unit
-
-
7-141
7