7 Other Functions
Name
Set-frequency-only ar-
rival signal
Set-frequency-only ar-
rival signal 2
 
Set-frequency-only arrival signal "FDT3"
Set-frequency-only arrival signal 2 "FDT4"
Frequency Match Detection (E20, E21, E27 = 87: FAR1FDT1)
This is an AND composite signal of FAR1 and FDT1, which turns ON when both the conditions are
established.
Over set frequency arrival signal 1 "FDT1"
Frequency arrival signal 1 (constant speed) "FAR1"
Frequency match detection "FAR1FDT1"
7-8-7
Power ON Time Over/RUN Time (ONT/RNT)
• If the total RUN time and power ON time of the inverter main circuit exceeds the time set at RUN
Time Over (RNT)/Power ON Time Over (ONT) Detection Level (E154), the inverter will output the
RUN time over/Power ON time over (RNT/ONT) signal.
Parameter No.
E154
7-92
E20, E21, E27 al-
Output signal
located data
FDT3
FDT4
E30
E31/E36
E30
Output frequency
E32
E31
Output frequency
0
Function name
RUN Time Over (RNT)/
Power ON Time Over
(ONT) Detection Level
Operation level
Range: 0.0 to 500.0
Hz
183
E31
185
E36
ON
E32
ON
ON
ON
ON
Data
0: Function disabled
1 to 9999 [x10h] (10 to 99.990 hours)
M1 Series Standard Type User's Manual (I669)
Frequency arrival
detection width
Range: 0.0 to 10.0
Hz
E30
E30
E30
E31/E36
E30
ON
t
ON
t
ON
t
ON
t
Default da-
Unit
ta
0
10 hex