Code
0
Digital Operator (Increment/Decre-
ment key) (No output frequency
takeover)
1
Analog voltage input (terminal
[AI1])
2
Analog current input (terminal [AI2]
(AII))
3
Analog voltage input (terminal
[AI1]) + analog current input (termi-
nal [AI2] (AII))
5
Analog voltage input (terminal AI2
(AIV))
7
UP/DOWN control
8
Digital Operator (Increment/Decre-
ment key) (Output frequency take-
over)
10
Pattern operation
13
Pulse train input or Frequency cal-
culation
21
RS-485 communications
22
Fieldbus (Reserved)
23
Support Tool
24
Multi-step Frequency
25
Jogging Frequency
30
PID Control Operator Process
31
PID Control Analog Process
33
PID Control UP/DOWN control
34
PID Control Communication Proc-
ess
36
PID Control Multi-Step Terminal
Process
255
Not Selected
Example: Frequency and PID Command Source Monitor (W29) = 000A hex
00
0A
→ 10 = Pattern operation
Hex
Hex
Data Format [74]: Integer Data (Positive), in 10 Hours
Example: 1st Remaining Time before the Next Motor Maintenance (M81) = 12,340 h
12340 ÷ 10 = 04D2
Data Format [76]: Operation Status 2
15
14
13
Drive
motor
type
M1 Series Standard Type User's Manual (I669)
Description
04
D2
H
H
h
12
11
10
9
8
Not used
8 Communications Functions
Remarks
Same as the selection for Frequency Reference Selection
(F01/C30)
7
6
5
4
Not
Selected
used
motor
During speed control
3
2
1
0
Control method
8
8-45