[d209 bit 1] Direction of return-to-origin operation 1: Reverse
Startup di-
rection of
return-to-
origin oper-
ation [d209
bit 0]
1: - direction
 Homing Reference Signal Selection (d211), Reference Signal for Homing
Offset (d212)
The reference signal for homing is to switch from the homing frequency to the homing creep fre-
quency. The reference signal for homing starts incrementing of the homing offset. Ordinarily, the
signal of the origin limit switch is taken as the reference signal for homing and the Z phase signal is
taken as the reference signal for homing offset (factory default). When return-to-origin is configured
using other signals, select the reference signal for homing and reference signal for homing offset
according to the table below. When Reference Signal for Homing Offset (d212) is set to other than
"0: Z pulse of position encoder", the reference signal for homing is not included in the configuration,
and so the Homing Reference Signal Selection (d211) setting is disabled.
Parameter No.
d211
d212
d214
M1 Series Standard Type User's Manual (I669)
rotation direction (+)
Initial
posi-
tion
- side
from
-OT
Startup direction of
origin
return-to-origin operation -
limit
switch
+ side
from
-OT
origin
limit
switch
Function name
Homing Reference Signal Se-
lection
Reference Signal for Homing
Offset
Creep Frequency
6 Vector Control and Applied Functions
When origin position < origin limit
Return-to-origin pattern diagram
Origin
Origin LS
Direction of return-to-origin operation -
Origin
Origin LS
Direction of return-
Startup direction of
to-origin operation -
return-to-origin operation -
Data
0: Z phase
1: Origin limit input (ORL)
2: Overtravel input in the posi-
tive direction (FOT)
3: Overtravel input in the nega-
tive direction (ROT)
0: Z phase
1: Origin limit input (ORL)
2: Overtravel input in the posi-
tive direction (FOT)
3: Overtravel input in the nega-
tive direction (ROT)
4: Stopper (Hit and stop)
0.1 to 590.0 Hz
switch position
+OT
+OT
Default
Unit
data
1
-
0
-
0.5
Hz
6-47
6