Omron M1 Series User Manual page 367

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Operation pattern stage No.
Stage 1
Stage 2
Stage 3
Stage 4
Stage 5
Stage 6
Stage 7
• The signal can be output at completion of cycle operation when the pattern operation stage is transi-
tioned to by allocating "16: TU (transition to pattern operation stage)" and "17: TO (pattern operation
cycle operation completion)" to output terminals DI1 to DI7. For details, refer to the operation exam-
ple figure below.
Precautions for Correct Use
When C21=0 is set and pattern operation is started by input via the FW/RV terminals turning
ON, the motor stops when the final stage ends even if the FW/RV terminals stay ON.
At this time, when the value of F01/C30 is changed without turning the FW/RV terminals OFF,
operation is immediately started according to the set frequency after the value is changed.
 Pattern operation setting examples
C21 (Pattern Op-
eration / Timed
Operation Mode
Selection)
0
This is illustrated as follows.
M1 Series Standard Type User's Manual (I669)
Operation
Rotation di-
Stage
time
No.
Set value
Set value
Stage 1
60.0
F
Stage 2
100
F
Stage 3
65.5
r
Stage 4
55.0
r
Stage 5
50.0
F
Stage 6
72.0
F
Stage 7
35.0
F
Output terminal signal
STG1
STG2
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
Accelera-
tion/deceler-
rection
ation time
Set value
2
1
4
3
2
4
2
5 Basic Settings
STG4
OFF
OFF
OFF
ON
ON
ON
ON
Operation (reference) fre-
quency
C05 Multi-step Frequency
Reference 1
C06 Multi-step Frequency
Reference 2
C07 Multi-step Frequency
Reference 3
C08 Multi-step Frequency
Reference 4
C09 Multi-step Frequency
Reference 5
C10 Multi-step Frequency
Reference 6
C11 Multi-step Frequency
Reference 7
5-37
5