Omron M1 Series User Manual page 304

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

4 Parameter List
Parameter
No.
2nd Online tuning 
A19
Function Selection
2nd Motor Armature
A20
Resistance
2nd Motor Motor Con-
A21
stant %R1
2nd Motor Motor Con-
A22
stant %X
2nd Slip Compensa-
A23
tion Gain for Driving
2nd Slip Compensa-
A24
tion Response Time
2nd Slip Compensa-
A25
tion Gain for Braking
2nd Rated Slip Fre-
A26
quency
A27
2nd Iron Loss Factor 1
2nd Magnetic Satura-
A30
tion Factor 1
2nd Magnetic Satura-
A31
tion Factor 2
2nd Magnetic Satura-
A32
tion Factor 3
4-138
Function name
Monitor or Data Range
0: Disable
1: Enable
0.00 to 500.0 A
0.00 to 50.00 %
0.00 to 50.00 %
0.0 to 200.0 %
0.01 to 10.00 s
0.0 to 200.0 %
0.00 to 15.00 Hz
0.00 to 20.00 %
0.0 to 300.0 %
0.0 to 300.0 %
0.0 to 300.0 %
Setting
Default
during
Unit
data
RUN
Availa-
0
-
ble
10.55
-
A
Availa-
3.17
%
ble
Availa-
11.47
%
ble
Availa-
100.0
%
ble
Availa-
0.12
s
ble
Availa-
100.0
%
ble
1
-
Hz
Availa-
2.86
%
ble
Availa-
92
%
ble
Availa-
84.2
%
ble
Availa-
70.5
%
ble
M1 Series Standard Type User's Manual (I669)