6-12 Overtorque/Undertorque Function
6-12-1
Overtorque/Undertorque Function Settings
Use this function to detect that the estimated motor output torque value exceeded the set level and
output the overtorque signal.
• To enable detection of the overtorque state, allocated "46: OTQ (Over/under torque signal) (NO con-
tact)" to Output Terminal [DO1] Function Selection (E20), Output Terminal [DO2] Function Selection
(E21) or Output Terminal [ROA, ROB] Function Selection (E27). Detection of the undertorque state
also can be enabled by allocating "1046: OTQ (Over/under torque signal) (NC contact)."
• The overtorque/undertorque ON signal is output when the torque value calculated by the inverter or
the torque command value is at the set level of torque detection (operation level) or higher, and con-
tinues for the set time of torque command detection (timer time) or longer. The overtorque/undertor-
que signal is turned OFF when the torque calculation value becomes "operation level - 5% of the
motor rated torque or lower."
• The operation level can be set separately to each of the four quadrants, and the state at accelera-
tion/deceleration and constant speed also can be selected.
• For calculating the overtorque and undertorque levels in this function, the motor rated torque is tak-
en to be 100%.
• Use this function to detect the brake release signal of an elevator, or if the load applied to the load
machine is abnormally high.
Parameter No.
E20, E21
E27
E78
E80
E196
E197
E79
E198
M1 Series Standard Type User's Manual (I669)
Function name
Output Terminal [DO1] Func-
tion Selection, Output Termi-
nal [DO2] Function Selection
Output Terminal [ROA, ROB]
Function Selection
Overtorque/Undertorque De-
tection Level at Forward
Power Running
Overtorque/Undertorque De-
tection Level at Reverse
Regeneration
Overtorque/Undertorque De-
tection Level Reverse Power
Running
Overtorquee/Undertorque
Detection Level Forward Re-
generation
Torque detection 1 Detection
Timer
Overtorque/Undertorque De-
tection Condition Selection
6 Vector Control and Applied Functions
Data
46: OTQ (Overtorque)
1046: OTQ (Undertorque)
0 to 300
0 to 300
0 to 300
0 to 300
0.01 to 600.00
0: Output during acceleration/decel-
eration and constant-speed opera-
tion
1: Output only during constant-
speed operation
6
Default
Unit
data
-
-
100
%
100
%
100
%
100
%
10.00
s
1
s
6-85