7 Other Functions
Output frequency
PID output (MV)
PID Control Restart Frequency after
Stopping for Process Control (J17)
PID Control Sleep Frequency for Process Control (J15)
Feedback (PV)
Piping route
internal pressure
RUN command
Wakeup signal
• PID Control Restart Feedback Deviation after Stopping for Process Control (J23)
• PID Control Restart Delay Time after Stopping for Process Control (J24)
The inverter restarts when both of the following conditions are satisfied.
1. The discharge pressure falls, the frequency reference value of the PID controller output rises, the
Restart Frequency (J17) is exceeded, and the PID Control Restart Delay Time after Stopping for
Process Control (J24) elapses.
2. The difference between SV (command value) and PV (feedback value) becomes more than PID
Control Restart Feedback Deviation after Stopping for Process Control (J23), and the PID Control
Restart Delay Time after Stopping for Process Control (J24) elapses.
7-136
Acceleration time
setting
Starting
frequency
Command (SV)
"PID-STP"
Deceleration time
setting
PID Control
Sleep Timer
The MV rises again
for Process
when the pressure
Control (J16)
(PV) drops.
The pressure starts dropping
by opening the faucet.
ON
ON
M1 Series Standard Type User's Manual (I669)
The pressure rises
when inverter
operation is resumed.
Time