Omron M1 Series User Manual page 549

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Main Circuit
DC Voltage
Inverter
Output frequency
Power supply system
200 V
400 V
• During decelerating at momentary power failure "IPF2"
This parameter turns ON when Power Interruption Restart Mode Selection (F14) is 2 or 3, and the
Main Circuit DC Voltage falls below Continuous Running Voltage Level (H15) and the continuous
running state is established. This parameter turns OFF when power restores and the Main Circuit
DC Voltage becomes "the voltage set in H15 +10 V or higher."
This parameter turns ON even when Power Interruption Restart Mode Selection (F14) is 4 or 5 and
the Main Circuit DC Voltage falls below the undervoltage level. This parameter turns OFF when the
DC link bus voltage reaches "the undervoltage level +10 V or higher."
Parameter No.
E20, E21, E27
Main Circuit
DC Voltage
"IPF2"
M1 Series Standard Type User's Manual (I669)
Power failure
Function name
Output Terminal [DO1]
79: IPF2 (During decelerating at mo-
Function Selection,
mentary power failure)
Output Terminal [DO2]
Function Selection,
Output Terminal [ROA,
ROB] Function Selec-
tion
Power failure
Power restoration
Continuous Running Voltage Level (H15)+ α
Continuous Running Voltage Level (H15)
Undervoltage level
α
22 kW max.
5 V
10 V
Data
Power restoration
Continuous Running Voltage Level (H15 + 10V)
Continuous Running Voltage Level (H15)
Undervoltage level
7 Other Functions
30 kw min.
10 V
20 V
Default data
Unit
-
-
7-57
7