8 Communications Functions
Value
10.00 to 99.99 1,000 to 9,999
100.0 to 999.9 1,000 to 9,999
1,000 to 9,999 1,000 to 9,999
Example: Data Used Integrating Electric Power (W82) = 9,999 kW
9,999 = Mantissa part: 9,999 (270F hex), Exponent part: 2 = A70F hex →
Example: Data Used Integrating Electric Power (W82) = 999.9kW
999.9 = Mantissa part: 9,999 (270F hex), Exponent part: 1 = 670F hex →
Example: Data Used Integrating Electric Power (W82) = 99.99kW
99.99 = Mantissa part: 9,999 (270F hex), Exponent part: 0 = 270F hex →
Data Format [67]: RUN Command Source Monitor
Code
0
Digital Operator positive direction
terminal
1
Terminal command (FW or RV)
2
Digital Operator forward rotation
3
Digital Operator reverse rotation
4 to 20
Reserved
21
RS-485 communications
22
Fieldbus (Reserved)
23
Support Tool
Example: RUN Command Source Monitor (W28) = 0001 hex
00
01
→ 1 = Terminal command (FW or RV)
Hex
Hex
Data Format [68]: Frequency Reference Source Code
8-44
Mantissa part Exponent part 10 to the power of (exponent part - 3)
1
2
3
Description
0.01
0.1
1
Remarks
Same as the selection for RUN Command Selection (F02/
E102)
M1 Series Standard Type User's Manual (I669)
A7
0F
Hex
Hex
67
0F
Hex
Hex
27
0F
Hex
Hex