Item
Parameter
No.
No.
6_06
X25
6_07
X26
6_08
X27
6_09
X28
6_10
X29
6_11
X30
M1 Series Standard Type User's Manual (I669)
Item
Latest Alarm Info.
0000Hex to
Running Status 1
FFFFHex
Latest Alarm Info. Cu-
0 to 655,350 hours
mulative Ope. time
0 to 9999
Latest Alarm Info.
1000 to 6553 [x10
Number of Startups
LED]
Latest Alarm Info.
Main Circuit DC Volt-
0.0 to 999.0 [V]
age
Latest Alarm Info. In-
ternal Air Tempera-
20 to 125 [°C]
ture
Latest Alarm Info.
Heat Sink Tempera-
20 to 125 [°C]
ture
Range
The operation status is displayed by a
four-digit hexadecimal.
0000 to FFFF hex
Bit15: BUSY (During function code data
writing)
Bit14: -
Bit13: -
Bit12: RL (Communications effective)
Bit11: ALM (Alarm relay)
Bit10: DEC (During deceleration)
Bit9: ACC (During acceleration)
Bit8: IL (During current limiting)
Bit7: VL (During voltage limiting)
Bit6: TL (Torque limiting)
Bit5: NUV (Main circuit DC voltage es-
tablished)
Bit4: BRK (During braking)
Bit3: INT (Inverter shut down)
Bit2: EXT (During DC braking or during
pre-exciting)
Bit1: REV (During reverse operation)
Bit0: FWD (During forward operation)
The cumulative inverter run time (the
time when the main power supply is ON)
when an error occurs is displayed.
It is displayed alternately in the upper
digits and lower digits.
When the lower three digits are dis-
played, an h (hours) is displayed in the
lowermost digit.
The number of operations of the motor
selected when an alarm occurred (num-
ber of times the RUN command for the
inverter is turned ON) is calculated and
displayed.
If the monitor value is 10000 or above,
the x10 LED lights up and the value of
"monitor value/10" is displayed.
The Main Circuit DC Voltage of the inver-
ter is displayed.
The internal air temperature during the
occurrence of an alarm is recorded and
displayed. For 20°C and below, 20°C is
displayed.
Display unit: °C
The heat sink temperature during the oc-
currence of an alarm is recorded and dis-
played. For 20°C and below, 20°C is dis-
played.
Display unit: °C