Omron M1 Series User Manual page 165

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

1. Set 1st Frequency Reference Selection (F01).
Set "0: Operator" at 1st Frequency Reference Selection (F01).
2. Set 1st RUN Command Selection (F02).
Set forward rotation (2: Touch panel operation (forward)) or reverse rotation (3: Touch panel op-
eration (reverse)) at 1st RUN Command Selection (F02).
3. Set the output frequency.
Set the set frequency by the
Initially, it is recommended to set a low speed of about 5 Hz for safety.
4. Press the
The motor starts rotating with the RUN LED lit.
5. Check that there is no problem with the output frequency, motor rotation direction or inverter op-
eration displayed on the Digital Operator.
For the rotation direction of motor, refer to rotation direction (monitor mode: 3_06).
Parame-
ter No.
C99
1st Frequency Refer-
ence/1st Multi-step
Frequency Reference
0
F02
1st RUN Command
Selection
Monitor
mode
3_00
3_06
Key opera-
tion
M1 Series Standard Type User's Manual (I669)
/
key.
Function name
0.0 to 590.00 Hz
0: Operator (Direction of rotation input: termi-
nal block)
1: External signal (Digital input)
2: Operator (Forward rotation)
3: Operator (Reverse rotation)
4: RS-485 communication
5: Fieldbus (Reserved)
Name
Output frequency 1
Rotation direction
Data display example
When the output frequency "0.00" is not displayed, press the
key to display the output frequency.
Press the
displayed on the data display.
keys with the set frequency "0.00" displayed flashing.
Set value
0.00 to 99.99 to 590.0 [Hz]
: During forward rotation
: During reverse rotation
: During stop
Description
key. The monitor value of the frequency reference is
3 Operation and Test Run
Default
Unit
data
0
Hz
2
-
Data
3
3-21