Omron M1 Series User Manual page 507

Multi-function compact inverter
Hide thumbs Also See for M1 Series:
Table of Contents

Advertisement

Pa-
rame-
Item No.
ter
No.
5_10
W82
5_11
W83
5_12
W84
5_13
W95
5_14
W87
5_15
W88
5_16
W89
5_17
W85
5_18
W94
5_19
-
5_23
Z40
M1 Series Standard Type User's Manual (I669)
Item
Data Used Integrat-
0.001 to 9999
ing Electric Power
Number of Operator
0 to 9999 [errors]
Comm Errors
Contents of Operator
0 to 127
Comm error
Reserved
-
Inverter ROM Version
x.xx.xx
1 Main
Inverter ROM Version
x.xx.xx
2 Sub
ROM Version Opera-
0 to 9999
tor
Number of RS-485
0 to 9999
Errors
Contents of RS-485
0 to 127
Error
-
-
1st Cumulative Run
0 to 9999 [x10h]
Time
Range
The integrated electric power consumption
(1.000 = 100 kWh) × Display Coefficient for
Integrated Power (E51) is displayed as the in-
tegrated electric power data.
The setting range of Display Coefficient for
Integrated Power (E51) is 0.000 to 9999.
Display unit: None
If 9999 is exceeded, the display remains as
9999.
The decimal point position moves depending
on the size of the integrating electric power
data, and the display resolution changes. The
integrating electric power data can be reset
by setting parameter E51 to "0.000." Integra-
tion is not performed when 0.000 is still set.
The number of errors after turning ON the
power is accumulated and displayed. If the
number of errors exceeds 9,999, the value re-
turns to 0.
The latest errors that occur in the Digital Op-
erator are displayed in a decimal code.
-
x.xx (upper three digits) and xx (lower two
digits) are displayed alternately.
x.xx (upper three digits) and xx (lower two
digits) are displayed alternately.
The version of the Operator is displayed.
If the cumulative value of the number of er-
rors after turning ON the power reaches
9999, the value returns to 0.
The error code of the final communication er-
ror that has occurred in the SP-SN terminal is
displayed in hexadecimal.
-
The cumulative time of the 1st motor run time
is displayed.
Measurement range: 0 to 99,990 hours
(Cumulative operation time of motor = Dis-
play × 10 hours)
If 99,990 hours is exceeded, the value returns
to 0 and the calculation continues.
7 Other Functions
Display item
7-15
7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents