7 Other Functions
Item
Parameter
No.
No.
6_24
X38
6_25
X04
6_30
X108
6_31
X49
2 The last alarm
6_00
X60
6_01
X61
6_06
X65
7-22
Item
Latest Alarm Info.
0000Hex to
Running Status 3
FFFFHex
Latest Multiple Alarm
0 to 9999
Sub Code 2
Latest Alarm Info. Cu-
mulative Running
0 to 655,350 hours
Time
0 to 9999
Fault Counter
1000 to 6553 [x10
LED]
Last Info. Alarm Info.
0.00 to 99.99,
Output Frequency
100.0 to 590.0 [Hz]
Last Alarm Info. Out-
0.00 to 99.99,
put Current
100.0 to 655.3 [A]
Last Alarm Info. Run-
0000Hex to
ning Status
FFFFHex
Range
The running status 3 is displayed by a
four-digit hexadecimal.
0000 to FFFF hex
Bit15: ---
Bit14: OL (Overload warning)
Bit13: LOC (Light load detection)
Bit12: OL2 (Overload warning 2)
Bit11: OLP (During active drive)
Bit10: LIFE (Life warning)
Bit9: OHF (Fin Overheat warning)
Bit8: TRY (During retry)
Bit7: FAN (Fan operation signal)
Bit6: REF (RUN command source)
Bit5: THM (Thermal warning)
Bit4: IPF (During restart after instantane-
ous power failure)
Bit3: SETM (2nd motor selection)
Bit2: IRDY (Operation ready)
Bit1: FDT1 (Over set frequency arrival
signal 1)
Bit0: FAR1 (Constant speed arrival)
The sub code when multiple alarms oc-
curred is displayed.
The cumulative time of the inverter RUN
state is displayed.
The cumulative operation time is dis-
played alternately in the upper digits and
lower digits.
When the lower three digits are dis-
played, an h (hours) is displayed in the
lowermost digit.
The number of times the inverter trips is
displayed.
The number of times is saved in the EE-
PROM when the power is turned OFF.
Counting is performed from 0 to 65535,
and if 65535 times is exceeded, the dis-
play remains as 65535.
By setting "7: Clear alarm history" to Da-
ta Initialization (H03), the value is
cleared to 0.
The output frequency before slip com-
pensation is displayed in increments of
0.01 Hz. A value of 100.0 Hz or higher is
displayed in increments of 0.1 Hz.
The output current is displayed. A cur-
rent value of 100.0A or higher is dis-
played in increments of 0.1 A.
Display unit: A (Ampere)