Output frequency
(motor rotation speed)
Auto-resetting
7-4-4
Unattended Start Protection (USP Terminal)
• Use this function to have the inverter trip if the power supply is turned ON with the RUN command
ON in the inverter.
• When the RUN command is ON and multifunction input "USP" is ON when the power is ON, a run
operation error (alarm code: Er6, sub code: 30) is generated
• When the Er6 alarm is reset with the RUN command still ON, operation is started regardless of the
ON/OFF setting of "USP." (Example 1)
• If the RUN command turns ON after the power supply is turned ON, the inverter operates normally.
(Example 2)
• Power recovery restart prevention based on USP input is enabled only for a RUN command from
the terminal block.
Parameter No.
E01 to E05, E98,
E99
The operation of the power recovery restart prevention function is shown below.
(Example 1)
Power ON with RUN command ON
(Reset with Reset (RS))
Power supply
FW input
(Forward)
USP input
RS input
(Reset)
AL output
(Alarm signal)
Output frequency
M1 Series Standard Type User's Manual (I669)
Overvoltage/overcurrent detection
"TRY"
Function name
Input Terminal [DI1] to [DI7]
Function Selection
ON
ON
Pull-in*
Restart from
starting frequency
H05
*Example of the set frequency (E152 = 2)
Data
186: USP (Unattended start protec-
tion)
(Example 2)
RUN command after power ON (Nor-
mal operation)
Power supply
FW input
(Forward)
USP input
RS input
(Reset)
AL output
(Alarm signal)
Output frequency
7 Other Functions
Auto search
Default da-
Unit
ta
-
OFF
ON
ON
OFF
7
-
7-59