Disable / Re-Enable Interlocking Output (H9/C3) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

30.3

Disable / re-enable interlocking output (H9/C3)

Interlocking outputs (Type = Interlocking) can be individually disabled via this menu (and
collectively via menu H2/B3). The "Interlocking Combination" (Area / Point) is to be entered
to disable the output. Up to 100 interlocking outputs can be disabled in the whole system.
Disabled interlocking outputs are listed in menu H4/U1.
The LED Fault / Disablements "General disablements" (L10) is also indicating one or more
disabled interlocking outputs.
Action
"Menu"
Scroll to menu H9.
"↲"
Scroll to menu
C3
"↲"
Write the area number
and point (e.g. 001
and 01).
"↲"
"|"
"↲"
"ESC"
Text in display
H9 Interlocking outputs and inputs
C1 Activated interlocking outputs / inputs
C2 Activate / deactivate interlocking output
C3 Disable / re-enable interlocking output
C3 Disable / re-enable interlocking output
Disable
Interlocking output area: 000 point: 00
Disable
Interlocking output area: 001 point: 01
-- Re-enable list (1) ---------------------------------------------
Interlocking output area: 001 point: 01
-- Disable -----------------------------------------------------------
Interlocking output area: _ _ _ point: _ _
Re-enable list (1)
Interlocking output area: 001 point: 01
Disable
Interlocking output area: 000 point: 00
C3 Disable / re-enable interlocking output
167
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Interlocking outputs can
be disabled / re-enabled
via menu C3.
Write area number and
address and press "↲" to
disable, which will be
indicated with "√" and a
beep. The output will be
automatically shown in
the Re-enable list.
If the specified output
doesn't exist, it will be
indicated with "X"
instead of "√" and a
beep.
Use the soft key "|" to
toggle between Disable
and Re-enable list.
Select in the Re-enable
list with "▼" (in this
example there is only
one output) and press
"↲".
The re-enabled output
will disappear from the
list, indicated with a
beep.
Continue as above or
press "ESC".
Scroll to another menu
or press "ESC".

Advertisement

Table of Contents
loading