Routing Equipment / Ase (H2/B5) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

23.5

Routing Equipment / ASE (H2/B5)

Disabled outputs are listed in menu H4/U1.
Notes: Outputs for routing equipment (Fire Brigade TX and Fault TX) can be disabled and
re-enabled via this menu however disabling and re-enabling is always carried out via the
ASE itself. Can be useful during an installation and commissioning, when only local alarms
are required.
Disabled output for routing equipment is indicated by LEDs Fault / Disablements "General
disablements" and "Fire Brigade TX".
Disabled output will stay disabled until re-enabled again via this menu.
Action
"Menu"
Scroll to menu H2.
"↲"
Scroll to menu B5.
"↲"
"↲"
42
Disable routing equipment from the FDCIE is not permitted, it must be disabled from the ASE itself.
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B5 Routing equipment
Disable Routing equipment
Fire
Fault
Disable routing equipment
Fire
Fault
-- Disabled routing equipment ---------------------------------
Fire alarm routing
42
121
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Via menu B5 the
standard outputs (fire
and fault) for routing
equipment can be
disabled.
Use "◄", "►"to toggle
between:
Fire
Fault
Press "↲" to disable,
which will be indicated
with "√" and a beep.
The "type" will be
automatically shown in
the Re-enable list
Use the soft key "|" to
toggle between Disable
and Disabled.

Advertisement

Table of Contents
loading

Table of Contents