Output (H2/B2) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

23.2

Output (H2/B2)

All programmable outputs in the FDCIE and outputs in units connected to the COM loops
(except outputs of type "Alarm device") can be individually disabled.
If you try to disable an output of type "Alarm device" it will be treated as if it does not exist,
see below.
Disabled output: Even if its control expression (trigger condition) is fulfilled (true), the
output will not be activated.
Action
"Menu"
Scroll to menu H2.
"↲"
Scroll to menu B2.
"↲"
Write loop unit technical
number and output
number,
(e.g. 000001 and 0).
"↲"
Text in display
H2 Disable or re-enable
B1 Zone or Zone/Address
B2 Output
B3 Output type
B4 Alarm devices
B5 Routing equipment
B6 Alert annunciation function
Escape
menu
B2 Output
Disable output
Loop unit 000000 output 0
Disable output
Loop unit 000000 output 0
-- Re-enable list (1) ---------------------------------------------
Loop unit 000001 output 0
Change type of
disablements
Change type of
disablements
115
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Via menu B2, a loop unit
output, C.U. output S0-
S3 / R0-R1 and exp.
board 4581 output can
be disabled.
Use the soft key
"Change type of
disablements" to toggle
between:
Loop unit output
Control unit output S
Control unit output R
Exp. board output
Write loop unit technical
number and output
number and press "↲" to
disable, which will be
indicated with "√" and a
beep. The output will be
automatically shown in
the Re-enable list
If the specified output
does not exist, it will be
indicated with "X"
instead of "√" and a
beep.
Use the soft key "|" to
toggle between Disable
and Re-enable list.