5. Tick the check box "With front" to select the control panel with front membrane, if
the control panel is not fitted with front display, do not tick the check box "with front".
6. Select the COM port to be used on your PC
7. Set the main board 5012 in "boot" mode, i.e. press and hold the "BOOT"
button (SW2) then press the "RESET" button (SW1) momentarily. Release
the "BOOT" button, the Main board LED "D24" is turned off whilst the Main
board is in "boot" mode.
8. Click "Start" to start the download. Another dialog box opens when display is fitted.
9. Set the MMI board 5015 in "BOOT" mode, i.e. press and hold the "BOOT" button
(SW2) and press the "RESET" button (SW1) momentarily. Release the "BOOT"
button, the MMI board LED "D18" will be turned off and the buzzer is turned on
while the MMI board is in "boot" mode.
10. Click "OK", the buzzer is turned off and the download continues. The download
status is indicated by the progress bar.
11. When the progress bar has finished to the end of the bar, the download will be
completed and the following dialog box opens:
12. Click "Yes" and the Control Unit will restart.
38
If several USB ports are used on your PC, and you want to find which COM port is connected to the panel, go to
Device Manger and look for EBL G3 Serial Port (COM#) under Ports, # will be the COM port number.
. Do not click "Start" yet.
38