Activate Interlocking Output (H9/C2); Reset Interlocking Output (H9/C3); Disable Interlocking Output (H9/C4); Re-Enable Interlocking Output (H9/C5) - Panasonic EBL128 Planning Instructions

Fire alarm system
Hide thumbs Also See for EBL128:
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01090
Rev: 3
11.3.2
11.3.3
11.3.4
11.3.5
11.4

Activate interlocking output (H9/C2)

Even if the control expression for an interlocking output is not
fulfilled (true), the output can be manually activated via this menu.
The "Interlocking Combination" (Area / Point) is to be entered to
activate the output. The corresponding interlocking input will be
"monitored" in the same way as if the output was activated by its
control expression.
Reset has to be performed via menu H9/C3.

Reset interlocking output (H9/C3)

Activated interlocking outputs are listed here. Use "↑" "↓" to scroll
between the "Interlocking Combinations" (Area / Point).
Interlocking output activated via its control expression and latching
output selected: The output has to be reset via this menu.
Interlocking output activated via its control expression and latching
output not selected: The output can be reset via this menu.
Interlocking output activated via menu H9/C2: The output has to be
reset via this menu.

Disable interlocking output (H9/C4)

Interlocking outputs (i.e. Output Type = Interlocking) can be disabled
via menu H9/C4. A disabled output will stay in (or return to) the
normal condition for the output respectively.
Combination" (i.e. Area / Point) is to be entered to disable the output.
If "00/00" is entered, all interlocking outputs will be disabled.

Re-enable interlocking output (H9/C5)

Interlocking outputs (i.e. Output Type = Interlocking) can be re-
enabled via menu H9/C5.
Disabled interlocking outputs are listed in menu H9/C5. Use "↑" "↓"
to scroll between the "Interlocking Combinations" (i.e. Area / Point)
or type it via the key-pad.
If "00/00" is entered, all interlocking outputs, disabled via menu
H9/C4 and "00/00", will be re-enabled.

Interlocking control expressions

A programmable output control expression can contain "interlocking"
trigger conditions ("Functions") numbers 14-17 (see chapter "Control
expression", page 69), i.e. one or more outputs can be activated when
one or more interlocking inputs are activated.
EBL128 Planning Instructions V1.1.x
78
The "Interlocking

Advertisement

Table of Contents
loading