Main board 5012 is backward compatible with 5010 and can be connected to an
•
existing TLON network with software ≥ V2.10.4.
MMI board 5015 is backward compatible with 5011.
•
Higher stabilised supply voltage results in approximately 55% longer loop length.
•
•
Improved monitoring due to accurate measuring the loop resistance which
increases the reliability.
Redundant communication (only software V3.x.x) and power supply for display
•
units. Other Connection and wiring are identical.
•
Large number of fuses have been replaced with PTC resettable electronic fuses
e.g. supervised voltage output. Remaining fuses uses M205 ceramic tube fuses.
•
Easy and quick repair with individual loop boards 5017 with connectors
Isolated USB interface to avoid generating earth fault if the PC is connected without
•
external isolator.
Replace jumper links to activate service signal in TLON applications by
•
pushbuttons.
5012 and 5015 are Compliant with the latest Australian standards AS7240.2:2018
•
and AS7240.4:2018.
Must use software ≥ V2.10.4.
•
5012 PCB layout and terminations are shown in Figure 9 below.
1. J9, connection for 458X expansion boards
Figure 9 Main Board 5012