29.5

Safe Shut Down of Control Unit (H8/S5)

It's not recommended to power down a Control Unit (i.e. no 230 V
without first performing a safe shut down of the Control Unit. Safe shut down will save the
SSW in a Flash ROM and put the CPUs at rest.
If no safe shutdown is performed, it may also generate a fault when you power up the
control unit again:
FAULT: Read/write site data (SSW), control unit xx"
It's highly recommended to perform a safe shut down after commissioning the installation
and calibrating the supervised outputs, changing passwords etc. in order to save the new
valid values and codes.
Safe shut down can be performed from any Control Unit and any Control Unit can be
selected. A Control Unit without a front has to be shut down from another Control Unit.
Note: By restart and power down, the Fault TX output(s) will be "activated".
Action
"Menu"
Scroll to menu H8.
"↲"
Scroll to menu S5.
"↲"
"▼"
"↲"
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S5 Safe shut down of control unit
Shut down control unit 00?
Ready for shut-down, break the power.
Automatic restart within xxx seconds!
xxx will start at 300 seconds and countdown to 000 before
the control unit will restart automatically. During the
countdown the buzzer will start sounding since the
communication between the Main and MMI boards has
stopped. (Can be silenced via push button "Silence buzzer".)
No
Yes
156
Operation Manual
FT1020G3 Rev 2.10.4
and no battery)
AC
Comments
According to chapter
"Access", see page 42.
Write control unit
number and press "▼"
to select "Yes".
The SSW is now saved
and the Main board and
MMI board CPUs are at
rest. You can now
power down the control
unit.
If not, the control unit
will restart automatically
after 300 seconds (5
minutes).