10 "Silence Buzzer; Silence Buzzer By Open Door; Silence Buzzer By The "Fb Bulgin Key - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

"SILENCE BUZZER"
10
The buzzer in FT1020G3 will sound for:
Fire alarm
Co-incidence alarm (2-zone or 2-unit dependent fire alarm): When only one zone or
one zone / address (alarm point) is in alarm status (0.8 / 5 sec.)
Pre-warning (0.8 / 5 sec.)
Quiet alarm (0.8 / 5 sec.)
Fault (continuous)
Disablements and Faults (1 sec. directly after the door to the FDCIE is closed.)
Activated interlocking input (0.8 / 0.8 sec.), if this option is selected via EBLWin.
Activated technical warning (0.5 / 10 sec.), if this option is selected via EBLWin.
Delayed alarm
Press "SILENCE BUZZER" button to silence the buzzer.
In case of a new alarm or if the push button "SILENCE BUZZER" is pressed again, the
buzzer will automatically re-sound.
10.1

Silence buzzer by open door

In EBLWin, the function "Silence Buzzer by Door Switch" can be selected. The buzzer will
then be disabled as long as the FT1020G3 cabinet door is open.
10.2

Silence buzzer by the "FB Bulgin Key"

Note: Valid only for the New Zealand convention.
When the New Zealand FB "Silence Alarms" Bulgin key switch (outside switch) is
turned ON (i.e. "Silence Alarms" position) the buzzer is silenced until the Bulgin key is
turned to the "Normal" position.
If there is a fault or disablement whilst the door to FT1020G3 is closed, the FT1020G3
buzzer will sound continuously directly after the door is closed, the fault and disablement
messages will be shown in the display.
Note: In the New Zealand convention, if any of the outputs for routing equipment ("Fire
Brigade TX" and "Fault TX") or outputs for alarm devices is disabled when the door of
FT1020G3 is being closed, the buzzer will sound continuously immediately after the door
is closed.
equipment left isolated"
the LCD. This information has higher priority than the normal fault messages and
disablements.
25
Incl. Heavy smoke/heat alarm, AA alarm and Acknowledged alarm (New Zealand only).
(0.4 / 0.4 sec.)
25
routing
equipment
"Alarm
and
left
isolated", "Fault
"Silence switch left active"
52
Operation Manual
FT1020G3 Rev 2.10.4
routing
will be shown in