Restart

21
A restart may delete some data in FT1020G3. Below follows an explanation of the different
data and abbreviations and a table describing the different reset alternatives and how the
data respectively is affected (cold or warm restart).
FF
= Fire alarms and Faults.
D
= Disablements
FFD
= Fire alarms, Faults and Disablements.
SSW
= Sensor min. / max. values & performance factor, supervised output calibration
values and event logs.
WASV
= Week Average Sensor Values
SSD
= Site Specific Data, i.e. all the installation programming created and
downloaded via EBLWin.
S/W
= Software, i.e. the EBL512 G3 system program.
The date & time and alarm counter value is stored in the memory of the real time clock, i.e.
the value will be retained also after the FDCIE has been powered down.
Note: After any restart, a new week average sensor value will be calculated within two
minutes for all the analogue smoke detectors. During these two minutes all fire alarms from
analogue smoke sensors will be suppressed. Thereafter a new average sensor value will
be calculated each week
21.1

Safe Shut Down

Safe shut down of Control Unit via menu H8/S6 will save the SSW data in a Flash ROM
in FT1020G3. Before the first "Safe shut down" of the Control Unit, this memory is empty.
After each "Safe shut down" the latest SSW data is saved (Safe shut down will not save
the week average sensor values).
When FT1020G3 is powered up, a restart takes place and the RAM (working memory) will
read the SSW data saved in the Flash ROM.
21.2

Restart Table

Table 18 below describes the different reset alternatives and how the data is affected.

Table 18 Data affected by restart

Action
Power down and then power up again. (both
mains and batteries disconnected)
Via menu H8/S5 Safe shut down of Control Unit.
Via RESET button on Main board 5012. If this
reset is done in the middle of a process,
also the SSW might be deleted.
Via RESET button on MMI board
Reset command via EBLWin or TLON
Manager.
Automatically after download of Site Specific
Data (SSD) via EBLWin.
Automatically after download of S/W via
EBLWin. The old S/W will be deleted.
Automatically due to trying to use auto boot
mode with a MMI board that doesn't support auto
boot mode
39
SSW previously saved with safe shut down is not deleted.
Data Deleted Data not Deleted
SSW, FFD,
SSD, S/W, SSW
Passwords
WASV
FFD, WASV
SSD, S/W, SSW
FFD, WASV
SSD, S/W, SSW
SSD, S/W, SSW
FFD, WASV
FFD, WASV
SSD, S/W, SSW
FFD, WASV
SSD, S/W, SSW
FFD, WASV,
SSD, S/W, SSW
passwords
FFD, WASV
SSD, S/W, SSW
107
Operation Manual
FT1020G3 Rev 2.10.4
Restart
Code
39
00 (+ 50)
00 (+50)
03 ( +53)
03
53
03 (+53)
25
00 (+50)
15