During the Acknowledgement Period (10-120 sec.), the following information (a list if many)
is shown in the FDCIE display:
LAA zone zz, activated
dd-mm-yyyy hh:mm
Menu
During the Investigation Period (1 - 9 min.), the following information (a list if many) is
shown in the FDCIE display:
LAA zone zz, investigation in progress
dd-mm-yyyy hh:mm
Menu
Note: The Local Alarm Acknowledgement Unit (4445) is the newer version of the
discontinued Alarm Acknowledgement Module (3340). In software ≥ V2.2.0, the Australian
AAFC function is moved to the obsoleted units and replaced by the LAA. The function of
AAFC and LAA are identical, only the wall control unit is different.
15.9

Quiet Alarm

Quiet alarm is an alarm type that can be programmed via EBLWin for analogue smoke
detectors. The quiet alarm is self-resetting alarm (non-latching), it is only displayed on the
LCD and is not activating any general alarm functions.
This feature is used in AS1668 supply air fan / stair pressurization fan control applications
or in residential units as a non-latching smoke detector alarm.
In AS1668 supply air fan applications, the type "Quiet alarm" is used to set in EBLWin the
duct detector to be non-latching and resets automatically after the post timing
completed, post time can be configured in EBLWin using a specific time signal period. The
I/O module 4461 must be selected as "4461 for fan".
In residential applications, an analogue smoke detector set to type "Quiet alarm" is used in
conjunction with the sounder base 3379 and LAAU 4445 (or ADF) as a local warning inside
the sole occupancy unit.
Quit alarm Indications and actions:
Detector LEDs are turned on (also a connected RIL).
LEDs "Fire" are blinking (0.4 / 0.4 sec.).
The buzzer sounds (0.8 / 5 sec.),
A Quiet alarm presentation (incl. a title "Quiet alarm") in the display.
Programmable outputs for quiet alarm are required e.g. 4461 outputs controlling fan
operation i.e. any output with a control expression containing the trigger conditions "Quiet
Alarm Zone" or "Quiet Alarm Zone Address" will display as shown below:
31
When the smoke clears up from the smoke chamber, the detector resets after predetermined time (normally 60
sec.)
65
Operation Manual
FT1020G3 Rev 2.10.4