26.5

Display Current Consumption on COM-loop (H5/A5)

The current consumption (an average value) for each COM loop can be displayed.
Action
Text in display
"Menu"
Scroll to menu H5.
H5 Service
A1 Calibration of supervised output
"↲"
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A5.
A5 Display current consumption on COM-loop
control unit: 00 (press ↵)
"↲"
Display current consumption on COM-loop:
"↲"
Please wait......
No reply from control unit.....
Current consumption on COM-loop: 0
control unit 00 is xxxx mA
"↲" or "ESC"
A5 Display current consumption on COM-loop
Note 1: No or very small current consumption (< 10 mA) cannot be presented correctly /
precisely since the accuracy is ±5 mA.
Note 2: If you get "No reply from control unit....." the control unit don't exist or don't answer.
0
140
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Write loop number and
control unit number and
press "↲".
If the control unit is
existing or doesn't
respond.
The current
consumption accuracy is
±5 mA. Information is
automatically updated
every 5 seconds
Scroll to another menu
or press "ESC".