6.3.6

User level 3A

After the door has been opened using 003 key ("Door open" symbol
field), the service / maintenance personnel have access to level 2B and after log on as
"Service personnel" (level 3A), access to all menus, i.e. same as level 2B and also to the
following menus:
Same menus as in access level 2B plus the following:
H5 Service
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
H8 Maintenance
S1 Disable / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of Control Unit
S6 Activate address in alarm mode
S7 Synchronize the Control Units
S8 Activate / Reset outputs
H10 Change password (In this case for "Service personnel".)
6.3.7

User level 3B

Used by Service / maintenance / commissioning engineers when a PC (i.e. EBLWin) is to
be connected to FT1020G3 for backup (upload), download of Site Specific Data and/or
download of software.
EBLWin require an EBLWin key (5094) to be plugged in the PC.
6.3.8

User level 4

Used by manufacturer or by personnel authorised by the manufacturer for re-initialisation
(reset) of the alarm counter, change software configurations, on-line status checking, etc.
An EBLWin key (5094) is required to be plugged in the PC.