Activate Address Setting Mode For Du (H5/A7) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

26.7

Activate Address Setting Mode for DU (H5/A7)

This function can be used by commissioning / service technicians to activate the address
setting mode
A specific unit or all units connected to one FDCIE can be activated for address setting.
Note: The units should be in operation and in quiescent condition, i.e. the units should have
already an address.
Action
Text in display
"Menu"
Scroll to menu H5.
H5 Service
A1 Calibration of supervised output
"↲"
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A7
A7 Activate address setting mode for DU
"↲"
Activate address setting mode for DU:
Control unit: 00, display unit: 00
"↲"
Address setting mode for display unit 00,
control unit 00 activated
"↲" or "ESC"
A7 Activate address setting mode for DU
43
As an alternative, the address setting mode can be activated via jumper "J4" inside the display unit.
in the following Display Units connected to the FDCIE:
43
External Presentation units
Alert Annunciation units
General Control Panel
All
142
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Write control unit
number, and the unit's
address or press "►" to
select "All" (i.e. all
display units on the
selected control unit).
The address can now be
edited in the display unit
(DU) respectively.
Scroll to another menu
or press "ESC".