Activate / Reset Outputs (H8/S8) - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

29.8

Activate / Reset outputs (H8/S8)

Via this menu, a loop unit output, control unit output and expansion board output can be
activated and reset.
Any output can be activated, which means the function can be tested. (Can also be done
via EBLWin.) This is including Addressable sounder base 3379 / 4479, wireless detector
4611, light indicator 4383, and all alarm devices 4480, 4481, 4482, 4487.
The selected output will be activated no matter if the control expression is true or not.
The selected output will be reset only if the control expression is false (not true). If the
control expression is true when you reset the output via menu H8/S8, the output will remain
activated until the control expression is false (not true) again.
Action
Text in display
"Menu"
Scroll to menu H8.
H8 Maintenance
"↲"
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
Scroll to menu S8.
S8 Activate / Reset output
"↲"
Write loop unit
technical number
and output (e.g.
-- Reset list (1) --------------------------------------------------
000001, 0).
"↲"
Activate
Loop unit 000000 output 0
Activate
Loop unit 000000 output 0
Loop unit 000001 output 0
Change type
of output
162
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Via menu S8, loop unit
output, control unit output
and expansion board output
can be activated and reset.
Use the soft key "Change
type of output" to toggle
between:
Loop unit output
Control unit output (S0-S3
& R0-R1)
Exp. board output.
Write loop unit technical
number and output number
and press "↲" to activate,
which will be indicated with
"√" and a beep. Output will
be shown in the Reset list
If the specified output doesn't
exist, it will be indicated with
"X" instead of "√" and a
beep.
Use the soft key "|" to
toggle between Activate and
Reset list.

Advertisement