Perform Monthly Test (H1)

22
The FT1020G3 and its associated equipment in a building must be tested on a regular
basis, please refer to the Australian Maintenance standard AS1851 for details regarding
monthly, quarterly and annual test.
In test mode, only the alarm points are tested, i.e. no outputs (no OWS or sounders) will
be activated during the test. (Alarm devices can be tested via menu H8/S4.)
If a real fire alarm is activated by an alarm point not in test mode, the normal fire alarm
functions will be activated, i.e. fire alarm presentation, outputs (sounders or OWS), routing
equipment (Fire Brigade TX) will be activated, etc.
Note: If FT1020G3 door is left open, the output(s) for external strobe or alarm bell might
be disabled (if set in EBLWin).
See also chapter "The information area priority order", page 22.
See also chapter "Perform ZONE TEST (Test mode) (H7)", page 148
Action
"Menu"
Menu H1, press "
"
"
"
"
"
"
"
Write zone no, (e.g.
001, 002, 003, 004)
"
"
The zone(s) will remain in test mode until the test mode is terminated. The test mode is terminated
in this menu or automatically one hour after the latest alarm test.
You will be automatically logged out 15 minutes after the latest "action" (using any of the keys) but the
zone(s) will remain in test mode until the test mode is terminated, see above.
Perform the test as quickly as possible, since the output(s) for routing equipment (Fire Brigade TX) are
disabled (also the parts of the zones in test mode, not visible for the test personnel, are disabled).
In order to shorten the testing time, any time delay for the detectors / zones in test mode will be
"disabled" i.e. fire alarm will be detected faster than normal conditions.
In the tested alarm point, the built-in LED will illuminate and the LEDs "Fire" in the FDCIE will illuminate
for approx. 10 seconds, then the alarm point will be automatically reset. There will be a test mode alarm
indication in the FDCIE display.
A detector in test mode can't generate a fault.
Text in display
H1 Perform monthly test
Check that all LEDs light up!
Press ↵
[ A l l d o t s a r e v i s i b l e ]
Zones to be set in test mode:
??? ??? ??? ??? Start test: ↵
Zones to be set in test
mode 001 002 003 004
Zones in test mode:
001 002 003 004
End test: ↵
110
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
The buzzer (in the
C.U.) sounds and all
dots in the display are
shown. All LEDs light
up, including LEDs in
units connected via
I/O Matrix board
4582.
Up to 4 zones can
be set in test mode
Press "
" to start
the test mode.
LED "Test mode" (L8)
will light up.
Perform the tests.