Sensitive Fault Detection Mode (H5/A2)

During commissioning, the "Sensitive fault detection mode" can be used to enable the
commissioning personnel to detect the faults faster than normal mode. The time delay for
each fault will then be reduced, i.e. you may find some faults now instead of later.
When the "Sensitive fault detection mode" is turned on, it is indicated by the LED Routing
equipment "Fault TX activated", "Fault" output for routing equipment is "activated" and the
search symbol
Note: Don't forget to turn off this mode after the commissioning.
Action
Text in display
"Menu"
Scroll to menu H5.
H5 Service
A1 Calibration of supervised output
"↲"
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in control unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Scroll to menu A2.
A2 Sensitive fault detection mode
Sensitive fault detection mode is not active
"↲"
Press ↲ to activate
"↲"
Sensitive fault detection mode was activated
Press ↲ to deactivate
Sensitive fault detection mode is not active
"↲"
Press ↲ to activate
A2 Sensitive fault detection mode
"ESC"
appears in the symbol area of the display.
137
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Scroll to another menu
or press "ESC".